VB12L-40 Magnetic RCBOPDF
VB12L-40 series magnetic tripping type RCBO mainly applies to the circuit of AC 50Hz, rated voltage 240V, rated current up to 40A. When electric shock occurs to human, leakage current or voltage in grid exceeds stipulated values, RCBO cuts off the fault power in a very short time to protect the safety of human and electrical equipments, it also owns the functions of overload and short circuit protection. In addition, it can switch on and off non frequently the electrical facilities and lighting circuit while the circuit works well.
Conforms to
IEC/EN61009-1 & 61009-2-1
Types |
Values |
Rated voltage(Un) |
240VAC |
Rated current(ln) |
6A,10A,16A,20A,25A,32A |
Rated residual operated current(l△n) |
0.03A,0.1A,0.3A |
Rated residual non tripping current(l△no) |
0.5l△n |
DC component |
AC type, A type |
Poles |
1P+N |
Instant tripping type |
B type,C type |
Rated short circuit breaking capacity(lcn) |
6000A |
Rated residual making and breaking capacity(l△m) |
500A |
Breaking time of residual operated current |
See Form2 and 3 |
Over current protection properties |
See Form4, Diagram1 and 2 |
Mechanical and electrical life |
SeeForm5 |
Connection wire |
SeeForm6 |
Tightening torque |
1.5N.m |
Nominal temperature ℃ |
30 |
Operated ambient temperature ℃ |
-25~+40 |
Stored ambient temperature ℃ |
-25~+70 |
Pollution level |
2 |
Protection level |
IP20 |
Mounting type |
Ⅱ |